12 SCADA Communications
P15D/EN TM/B
12-11
Sr. No. INF Description GI TYP COT FUN
3 Semantics of INFORMATION NUMBER : Fault indications in monitor direction
64 start/ pick-up R X 2 1,7,9 160
65 start/ pick-up Y X 2 1,7,9 160
66 start/ pick-up B X 2 1,7,9 160
68 General Trip - 2 1,7 160
69 Trip R - 2 1,7 160
70 Trip Y - 2 1,7 160
71 Trip B - 2 1,7 160
84 General start/ pick-up X 2 1,7,9 160
90 Trip I>1 - 2 1,7 160
91 Trip I>2 - 2 1,7 160
103 I>2 pick-up X 2 1,7,9 126
104 Trip I>3 - 2 1,7 126
105 I>3 pick-up X 2 1,7,9 126
117 I>1 pick-up X 2 1,7,9 126
123 Trip IN>1 - 2 1,7 126
124 Trip IN>2 - 2 1,7 126
125 Trip IN>3 - 2 1,7 126
143 IN>1 pickup X 2 1,7,9 126
144 IN>2 pickup X 2 1,7,9 126
145 IN>3 pickup X 2 1,7,9 126
177 I< - 2 1,7 126
178 I< pickup X 2 1,7,9 126
200 Th Alarm - 2 1,7 126
202 Th Trip - 2 1,7 126
225 CLP - 2 1,7 126
21 CLP Timer in progress - 2 1,7 124
22 Test Mode - 2 1,7 124
Sr. No. INF Description GI TYP COT FUN
5 Semantics of INFORMATION NUMBER : Measurands in monitor direction
147 Measurand I
N
- 3 2, 7 160
148 Measurand I
L 1,2,3
- 9 2, 7 160
155 Th State - 9 2,7 160
Note: The measurands transmitted by the relay are sent as a proportion of 2.4 times of the rated value of
the analogue value.
Sr.
No.
INF Description GI TYP COT FUN
6 Semantics of INFORMATION NUMBER: Fault list in monitor direction
0 List of Recorded DR - 23 31 160