5 Configuration
P50 Agile P15D
5-22
P15D/EN TM/B
DATE AND TIME
Note:
*** By using the Left arrow key (
) or Right arrow key (
) the relay will return to Main Menu.
2.3.6 CONFIGURATION MENU
2.3.6.1 Edit settings
CONFIGURATION
Password protected window for “CONFIGURATION” settings i.e.
Restore Defaults, Active Settings, Setting Group1, Setting Group 2,
System Configuration, Over Current, Earth Fault, Thermal Overload,
Cold Load Pick-up, Measure’t Setup, Under Current protection and
Setting Value.
Press the Left arrow key () to move to the next option.
Password = 0000
Press the Edit Key, the number will start blinking.
Enter the previously set password by using the Plus / Up arrow key (+
/) or the Minus / Right arrow key (- /). The Password setting range
is 0000 to 9999. The Default Password is “0000”
After editing the Password press the Edit Key, the number will stop
blinking.
Press the Left arrow key () to move to the next option.
Restore Defaults
No Operation
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired Restore Defaults can set i.e. No Operation / All
Settings / Setting Group 1 / Setting Group 2.
After selecting the desired Restore Default setting, press the Edit Key
the text will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
Active Settings
Group 1
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired Active Setting can set i.e. Group 1 / Group 2.
After selecting the desired Active Settings press the Edit Key, the text
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *