P50 Agile P15D
5 Configuration
P15D/EN TM/B
5-31
2.3.9 COMMUNICATION MENU
2.3.9.1 Edit settings
COMMUNICATION
Password protected window for “COMMUNICATION settings i.e. RP1
Address, RP1 Baudrate, RP1 Parity and RP1 Timesync.
Press the Right arrow key () to move to the next option.
Password = 0000
Press the Edit Key, the number will start blinking.
Enter the previously set password by using the Plus / Up arrow key (+
/) or the Minus / Right arrow key (- /). The Password setting range
is 0000 to 9999. The Default Password is “0000”
After editing the Password press the Edit Key, the number will stop
blinking.
Press the Left arrow key () to move to the next option.
RP1 Address
001
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired RP1 Address can be set. The setting range is from 1 to
247 in steps of 1.
After editing the desired RP1 Address press the Edit Key, the number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
RP1 Baudrate
57600
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired RP1 Baudrate can be set. i.e. 9600 / 14400 / 19200 /
28800 / 38400 / 57600
After editing the desired RP1 Baudrate press the Edit Key, the number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
RP1 Parity
Even
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired RP1 Parity can set i.e. Even / Odd / None.
After selecting the desired RP1 Parity press the Edit Key, the text will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
RP1 Timesync
Enabled
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired RP1 Timesync can set i.e. Enabled / Disabled
After selecting the desired RP1 Timesync press the Edit Key, the text will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *