5 Configuration
P50 Agile P15D
5-38
P15D/EN TM/B
I>1 tRESET
001.00
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 tRESET can be set. The setting range is from
000.00 to 100.00 in steps of 0.01.
After editing the desired I>1 tReset press the Edit Key, the number will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
I>1 2H Blocking
Enable
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 2H Blocking function can set i.e. Enable / Disable.
After selecting the desired I>1 Blocking press the Edit Key, the text will
stop blinking. **
Press the Left arrow key () to move to the next option. *
I>1 Current Set
1.00 A
The window displays the first setting of the Over Current menu.
Press the Left arrow key () to move to the next option.
SET For Save
RESET For Cancel
Press the SET / Left arrow key () to SAVE the changes.
Press the RESET key to CANCEL the changes.
OK
When the SET / Left arrow key () is pressed the relay will SAVE the
changes and this window will flash for moment. The control will return to
the Main Menu.
GROUP 1
Note:
#. If the function is set as enable then the relay will allow editing the settings of respective sub menus. If the
function is set as disable then the relay will not allow editing the settings of sub menus and will bypass the
protection function.
* The User can scroll the previous settings by using the Plus / Up arrow key (+ /
).
** After Editing any sub menus of the Over Current setting, If the SET/ Left (
) arrow key is pressed, the
Relay ask SET to SAVE the changes or RESET to CANCEL the changes.