SET For Save
RESET For Cancel
Press the SET / Left arrow key () to SAVE the changes.
Press the RESET key to CANCEL the changes.
OK
When the SET / Left arrow key () is pressed the relay will SAVE the
changes and this window will flash for moment. The control will return to
the Main Menu.
GROUP 1
2.3.12.2 Edit settings (if I>1 function is selected for IEC curves)
Overcurrent
By using the Plus / Up arrow key (+ /) or Minus / Right arrow key (-
/) select the Over Current setting menu in Group 1.
Press the Left arrow key () to move to the next option.
I>1 Function
IEC S Inverse
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 Function (Curve Selection) can be set i.e. Disable /
US ST Inverse / US Inverse / IEEE E Inverse / IEEE V Inverse / IEEE M
Inverse / UK LT Inverse / IEC E Inverse / IEC V Inverse / S Inverse (1.3
Sec) / IEC S Inverse and DT.#
After selecting the desired I>1 Function press the Edit Key, the text will
stop blinking.
Press the Left arrow key () to move to the next option.
I>1 Current Set
1.00 A
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 Current Setting can be set. The setting range is
from 0.20 to 2.50 in steps of 0.01.
After editing the desired I>1 Current Setting press the Edit Key, the
number will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
I>1 TMS
001.00
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 TMS can be set. The setting range is from 0.025 to
1.200 in steps of 0.005.
After editing the desired I>1 TMS press the Edit Key, the number will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *