SET For Save
RESET For Cancel
Press the SET / Left arrow key () to SAVE the changes.
Press the RESET key to CANCEL the changes.
OK
When the SET / Left arrow key () is pressed the relay will SAVE the
changes and this window will flash for moment. The control will return to
the main menu.
GROUP 1
Note:
#. If the function is set as enable then the relay will allow to edit the settings of respective sub menus. If the
function is set as disable then the relay will not allow to edit the settings.
* The User can scroll the previous settings by using the Plus / Up arrow key (+ /
).
** After Editing any sub menus of the System Configuration setting, If the SET/ Left (
) arrow key is pressed,
the Relay ask SET to SAVE the changes or RESET to CANCEL the changes.
2.3.12 GROUP 1 – OVERCURRENT SUB MENU
2.3.12.1 Edit settings (if I>1 function is disabled)
Overcurrent
By using the Plus / Up arrow key (+ /) or Minus / Right arrow key (-
/) select the Over Current setting menu in Group 1.
Press the Left arrow key () to move to the next option.
I>1 Function
Disable
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 Function (Curve Selection) can be set i.e. Disable /
US ST Inverse / US Inverse / IEEE E Inverse / IEEE V Inverse / IEEE M
Inverse / UK LT Inverse / IEC E Inverse / IEC V Inverse / S Inverse (1.3
Sec) / IEC S Inverse and DT. #
After selecting the desired I>1 Function press the Edit Key, the text will
stop blinking.
Press the Left arrow key () to move to the next option.