5 Configuration
P50 Agile P15D
5-44
P15D/EN TM/B
2.3.13.2 Edit settings (if IN>1 function is selected for IEC curves)
Earth Fault
By using the Plus / Up arrow key (+ /) or Minus / Right arrow key (-
/) select the Earth Fault setting menu in Group 1.
Press the Left arrow key () to move to the next option.
IN>1Function
IEC S Inverse
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 Function (Curve Selection) can set i.e. Disable /
US ST Inverse / US Inverse / IEEE E Inverse / IEEE V Inverse / IEEE M
Inverse / UK LT Inverse / IEC E Inverse / IEC V Inverse / S Inverse (1.3
Sec) / IEC S Inverse 1 and DT. #
After selecting the desired IN>1 Function press the Edit Key, the text will
stop blinking. **
Press the Left arrow key () to move to the next option.
IN>1Current Set
0.20 A
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 Current Setting can be set. The setting range is
from 0.10 to 2.50 in steps of 0.01.
After editing the desired IN>1 Current Setting press the Edit Key, the
number will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
IN>1 TMS
1.000
Press the Edit Key the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 TMS can be set. The setting range is from 0.025 to
1.200 in steps of 0.005.
After editing the desired IN>1 TMS press the Edit Key, the number will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
IN>1 tRESET
001.00
Press the Edit Key the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1tRESET can be set. The setting range is from
000.00 to 100.00 in steps of 0.01.
After editing the desired IN>1 tRESET press the Edit Key, the number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
IN>1 2H Blocking
Enable
Press the Edit Key, the text value will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 2H Blocking function can be set i.e. Enable /
Disable.
After selecting the desired IN>1 Blocking press the Edit Key, the text will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *

Related product manuals