5 Configuration
P50 Agile P15D
5-46
P15D/EN TM/B
IN>1Current Set
0.20 A
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 Current Setting can be set. The setting range is
from 0.10 to 2.50 in steps of 0.01.
After editing the desired IN>1 Current Setting press the Edit Key, the
number will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
IN>1 Time Dial
001.00
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 Time Dial can be set. The setting range is from
000.01to 100.00 in steps of 0.01.
After editing the desired IN>1 Time Dial press the Edit Key, the number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
IN>1 tRESET
001.00
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 tRESET can be set. The setting range is from
000.00 to 100.00 in steps of 0.01.
After editing the desired IN>1 tReset press the Edit Key, the number will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
IN>1 2H Blocking
Enable
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired IN>1 2H Blocking function can be set i.e. Enable /
Disable.
After selecting the desired IN>1 Blocking press the Edit Key, the text will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
IN>1Current Set
0.20 A
The window displays the first setting of the Earth Fault setting menu.
Press the Left arrow key () to move to the next option.
SET For Save
RESET For Cancel
Press the SET / Left arrow key () to SAVE the changes.
Press the RESET key to CANCEL the changes.
OK
When the SET / Left arrow key () is pressed the relay will SAVE the
changes and this window will flash for moment. The control will return to
the Main Menu.