5 Configuration
P50 Agile P15D
5-56
P15D/EN TM/B
2.3.15.3 Edit settings (For I>1, DT i.e. Definite Time is selected)
Cold Load Pickup
By using the Plus / Up arrow key (+ /) or Minus / Right arrow key (-
/) select the Cold Load Pickup setting menu in Group 1.
Press the Left arrow key () to move to the next option.
tcold Time Delay
07200
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired tcold Time Delay can be set. The setting range is from
00000 to 14400 in steps of 1.
After editing the desired tcold Time Delay press the Edit Key, the
number will stop blinking.
Press the Minus / Right arrow key (- /) to move to the next option.
tclp Time Delay
07200
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired tclp Time Delay can be set. The setting range is from
00000 to 14400 in steps of 1.
After editing the desired tclp Time Delay press the Edit Key, the number
will stop blinking.
Press the Minus / Right arrow key (- /) to move to the next option.
I>1 Status
Enable
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 Status can be set i.e. Enable / Block. #
After selecting the desired I>1 Status press the Edit Key, the text will
stop blinking.
Press the Left arrow key () to move to the next option.
I>1 Current Set
1.50 A
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 Current Set can be set. The setting range is from
0.20 to 4.00 in steps of 0.01.
After editing the desired I>1 Current Set press the Edit Key, the number
will stop blinking**.
Press the Minus / Right arrow key (- /) to move to the next option. *
I>1 Time Delay
001.00
Press the Edit Key, the number will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired I>1 Time Delay can be set. The setting range is from
000.00 to 100.00 in steps of 0.01.
After editing the desired I>1 Time Delay press the Edit Key, the number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
I>1 Current Set
1.50 A
The window displays the first setting of the I>1 Current Set of the Cold
Load Pickup setting.
Press the Left arrow key () to move to the next option.