UNDERCURR PROT
Password protected window for “UNDERCURRENT” Protection settings
Note:
The Group 2 Function for the setting System Configuration, over Current, Earth Fault, Thermal Overload, Cold
Load Pkp and under Current Protection is similar to Group 1.
2.3.18 SYSTEM DATA MENU
2.3.18.1 Edit settings
SYSTEM DATA
By using the Plus / Up arrow key (+ /) or Minus / Right arrow key (-
/) select the System Data setting menu.
Press the Left arrow key () to move to the next option.
Frequency
50Hz
Press the Edit Key, the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired system Frequency can be set i.e. 50Hz / 60Hz
After selecting the desired Frequency press the Edit Key, the text will
stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
Password = 0000
Press the Edit Key, the number will start blinking.
Enter the New password by using the Plus / Up arrow key (+ /) or the
Minus / Right arrow key (- /). The Password setting range is 0000 to
9999. The Default Password is “0000”
After editing the New Password press the Edit Key, the settable number
will stop blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
Com Port
USB
Press the Edit Key the text will start blinking.
By using the Plus / Up arrow key (+ /) or the Minus / Right arrow key (-
/) the desired Com Port can be set i.e. USB / RP
After selecting the desired Com Port press the Edit Key, the text will stop
blinking. **
Press the Minus / Right arrow key (- /) to move to the next option. *
Frequency
50Hz
The window displays the first setting of the System Data menu.
Press the Left arrow key () to move to the next option.