IS-300CR INVERTER POWER SUPPLY
990-418 E-1
APPENDIX E
EtherNet/IP
TM
Communications
Section I. Introduction
Introduction
This appendix will provide the instructions on how to setup the connectivity from an Allen Bradley
®
PLC to the Amada Miyachi IS-300CR Inverter Power Supply via an EtherNet/IP
TM
bus controller
(X20BC0088). The machine builder / user who integrates the IS-300CR EtherNet/IP
TM
communication installation kits should have some working knowledge with the Allen Bradley
®
PLC and
the RSLogix5000 programming logics.
The EtherNet/IP
TM
bus controller (X20BC0088) that is built into the IS-300CR, includes modules that
serve as communication adapters between the IS-300CR and the Allen Bradley
®
PLC. This allows the
reading and writing of the digital I/Os, analog I/Os and serial communication screen data to / from the
IS-300CR Inverter Power Supply via any EtherNet/IP
TM
protocol scanner like an Allen Bradley
®
master
PLC.
The IS-300CR EtherNet/IP
TM
support files are located on the USB Flash Memory that was shipped with
your Power Supply (AMYA # 4-40965-01). These support files include:
A functional sample program of the Allen Bradley
®
1769-L32E PLC that communicates to the Bus
Controller. This file is located under the folder:
\IS_Series_AB_EthernetIP\RSLogix_PLC (40368)\IS_1769_L32E.ACD
An **.L5K digital & analog I/O configurations file. This file is located under the folder:
\IS_Series_AB_EthernetIP\RSLogix_PLC (40368)\Importable\IS_1769-L32E.L5K
Data Types / Tags / Program Routines. These files are located under the folders:
\IS_Series_AB_EthernetIP\RSLogix_PLC (40368)\Importable\DataTypes
\IS_Series_AB_EthernetIP\RSLogix_PLC (40368)\Importable\Tags
\IS_Series_AB_EthernetIP\RSLogix_PLC (40368)\Importable\Programs
IS-300CR Weld Schedule Controller Windows Application. This file is located under the folder:
\IS_Series_AB_EthernetIP\Windows_EthernetIP_WeldControl (40713)\
Panel View Plus HMI. This Factory Talk ME Runtime support file is located under the folder:
\IS_Series_AB_EthernetIP \PanelViewPlus_EthernetIP_WeldControl (40715)\
This appendix will provide the user;
How to setup the IP address of the EtherNet/IP
TM
bus controller via webserver.
Two available options for configuring the bus controller communication with Allen-Bradly
®
PLC Software:
a. Automatic configuration (via a pre-generated .L5K configuration)
b. Manual configuration (user configured).
How to import data types, tags, program routines to a PLC.