4 Function tables - summary of setup functions
Note: the order in which the functions appear on the display may not be exactly as shown below.
The availability and order of functions is determined by choice of function settings and options
fitted.
Functions in this first table are available in FUNC or CAL mode
Display Function Range Default Your
record
Ref/Page
AxLo Low setpoint value for
designated alarm relay x
Any display
value or OFF
OFF See
4.1
5.1 / 18
AxHi High setpoint value for
designated alarm relay x
Any display
value or OFF
OFF See
4.1
5.2 / 18
AxHY Hysteresis value for the
designated alarm relay x.
0 to 9999 10 See
4.1
5.3 / 19
Axtt Trip time delay for the
designated alarm relay x.
0 to 9999 0 See
4.1
5.4 / 20
Axrt Reset time delay for the
designated alarm relay x.
0 to 9999 0 See
4.1
5.5 / 20
Axn.o
or
Axn.c
Alarm relay x action to
normally open (de-energised) or
normally closed (energised)
Axn.o or
Axn.c
Axn.o See
4.1
5.6 / 20
AxSP
or
Axt1
etc.
Relay operation independent
setpoint or trailing setpoint
(
∗
Optional)
AxSP or
Axt1 etc.
AxSP See
4.1
5.7 / 21
Ax.SP PI relay control setpoint Any display
value
0 See
4.1
7.2 / 46
brGt Display brightness level 1 to 15 15 5.9 / 21
duLL Display remote brightness
switching
0 to 15 1 5.10 / 22
P.SEt Preset value Any display
value
0 5.11 / 22
(
∗
Optional)—this function will only be accessible if the relevant option is fitted
PM4IVMAN-2.4-0 11 of 56