Functions in this second table are available only in CAL mode or if ACCS is set to ALL
Display Function Range Default Your
record
Ref/Page
Ax
OPEr
Relay operation mode, alarm or
PI control
Ax.AL or
Ax.tP or
Ax.Fr
Ax.AL See
4.1
5.8 / 21
ctrI
SPAN
PI relay control span Any display
value
100 See
4.1
7.3 / 46
Ax.PG PI relay proportional gain -32.767 to
32.767
0.010 See
4.1
7.4 / 47
Ax.IG PI relay integral gain -32.767 to
32.767
0.000 See
4.1
7.5 / 48
Ax.IL PI relay integral control low
limit
0.0 to 100.0 100.0 See
4.1
7.7 / 50
Ax.IH PI relay integral control high
limit
0.0 to 100.0 100.0 See
4.1
7.6 / 49
Ax.bs PI relay control output bias 0.0 to 100.0 50.0 See
4.1
7.8 / 50
Ax.dc PI relay control cycle period 0 to 250 10 See
4.1
7.9 / 50
Ax.dr PI relay on duration 0.0 to 25.0 1.0 See
4.1
7.12 / 53
bAr_ Bargraph low value (seen only
on bargraph display
instruments)
Any display
value
0 5.12 / 22
bAr~ Bargraph high value (seen only
on bargraph display
instruments)
Any display
value
1000 5.13 / 23
bAr
tYPE
Bargraph type for instruments
with bargraph display (seen
only on bargraph display
instruments)
bAr, S.dot,
d.dot,
C.bAR or
r.dot
bAr 5.14 / 23
dGOP Digital output option mode
(
Optional)
bcd, b.SCL,
bin or bin2
bin2 5.15 / 24
dG.OP Digital output option polarity
(
Optional)
AIo or AHi AIo 5.16 / 24
bcd
Strt
Digital output option BCD start
position (
Optional)
0, 1 or 2 0 5.17 / 24
diG_ Digital output option low value
(
Optional)
Any display
value
0 5.18 / 25
diG~ Digital output option high value
(
Optional)
Any display
value
1000 5.19 / 25
REC_ Analog output option low
display value (
Optional)
Any display
value
0 5.20 / 25
(
Optional)—this function will only be accessible if the relevant option is fitted
12 of 56 PM4IVMAN-2.4-0