5.18 Digital output option low value
Display: diG_
Range: Any display value
Default Value: 0
Seen only with the 16 bit digital output option. Refer to the separate “PM4 Panel Meter Optional
Output Addendum” booklet supplied when this option is fitted. Accepts any valid display value.
Determines the low scaling point for the b.SCL mode and has no effect on other modes. See
example which follows in 5.19.
5.19 Digital output option high value
Display: diG~
Range: Any display value
Default Value: 1000
Seen only with the 16 bit digital output option. Refer to the separate “PM4 Panel Meter Optional
Output Addendum” booklet supplied when this option is fitted. Determines the high scaling point
for the b.SCL mode and has no effect on other modes.
Example: If diG_ is set to 0 and diG~ is set to 65535 (2
16
− 1) then the retransmission
will not be scaled i.e. a display of 2 will cause a retransmission of 2. If diG~ is now changed to
32767 (2
15
− 1) then a display of 2 will cause a retransmission of 4 (note: rounding may occur
on retransmission).
5.20 Analog output option low value
Display: REC_
Range: Any display value
Default Value: 0
Seen only when analog retransmission option fitted. Refer to the separate “PM4 Panel Meter
Optional Output Addendum” booklet supplied when this option is fitted for wiring details and link
settings. Displays and sets the analog retransmission (4–20mA, 0–1V or 0–10V, link selectable)
output low value (4mA or 0V) in displayed engineering units. To set the analog output low value
go to the REC_ function and use the ^ or v push buttons to set the required value then press
F to accept this selection.
Example:If it is required to retransmit 4mA when the display indicates 0 then select 0 in this
function using the ^ or v button.
5.21 Analog output option high value
Display: REC~
Range: Any display value
Default Value: 1000
Seen only when analog retransmission option fitted. Refer to the separate “PM4 Panel Meter
PM4IVMAN-2.4-0 25 of 56