Optional Output Addendum” booklet supplied when this option is fitted for wiring details and link
settings. Displays and sets the analog retransmission (4–20mA, 0–1V or 0–10V, link selectable)
output high display value (20mA, 1V or 10V) in displayed engineering units. To set the analog
output high value go to the REC~ function and use the ^ or v push buttons to set the required
value then press F to accept this selection.
Example: If it is required to retransmit 20mA when the display indicates 50 then select 50 in
this function using the ^ or v button.
5.22 Second analog output option low value
Display: REC_ Ch2
Range: Any display value
Default Value: 0
See REC_ function 5.20 for description of operation.
5.23 Second analog output option high value
Display: REC~ Ch2
Range: Any display value
Default Value: 1000
See REC~ function 5.21 for description of operation.
5.24 Display rounding
Display: drnd
Range: 1 to 5000
Default Value: 1
Displays and sets the display rounding value. This value may be set to 1 - 5000 displayed units.
Display rounding is useful for reducing the instrument resolution without loss of accuracy in ap-
plications where it is undesirable to display to a fine tolerance. To set the display rounding value
go to the drnd function and use the ^ or v push buttons to set the required value then press
F to accept this selection.
Example: If set to 10 the display values will change in multiples of 10 only i.e. display moves
from 10 to 20 to 30 etc.
5.25 Decimal point
Display: dCPt
Range: 0, 0.1 etc.
Default Value: 0
Displays and sets the decimal point. By pressing the ^ or v pushbutton at the dCPt function
the decimal point position may be set. The display will indicate as follows: 0 (no decimal point),
26 of 56 PM4IVMAN-2.4-0