18
EN
Servicing
•  Any person who is involved with working on or breaking into a 
refrigerant circuit should hold a current valid certificate from an 
industry-accredited assessment authority, which authorizes their 
competence to handle refrigerants safely in accordance with an 
industry recognized assessment specification.
•  Servicing shall only be performed as recommended by the equipment 
manufacturer. Maintenance and repair requiring the assistance of 
other skilled personnel shall be carried out under the supervision of 
the person competent in the use of flammable refrigerants.
Checks to the area
Prior to beginning work on systems containing flammable refrigerants, 
safety checks are necessary to ensure that the risk of ignition is 
minimised. For repair to the refrigerating system, the following 
precautions shall be complied with prior to conducting work on the 
system.
Work procedure
Work shall be undertaken under a controlled procedure so as to minimise 
the risk of a flammable gas or vapour being present while the work is 
being performed.
General work area
All maintenance staff and others working in the local area shall be 
instructed on the nature of work being carried out. Work in confined 
spaces shall be avoided. The area around the workspace shall be 
sectioned off. Ensure that the conditions within the area have been made 
safe by control of flammable material.
Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior 
to and during work, to ensure the technician is aware of potentially 
flammable atmospheres. Ensure that the leak detection equipment being 
used is suitable for use with flammable refrigerants, i.e. non-sparking, 
adequately sealed or intrinsically safe.
Presence of fire extinguisher
If any hot work is to be conducted on the refrigeration equipment or 
any associated parts, appropriate fire extinguishing equipment shall be 
available to hand. Have a dry powder or CO
2
 fire extinguisher adjacent to 
the charging area.