GG2 COMMUNICATIONS USER MANUAL
GG2B032
Version 1 JULY/2020
Uncontrolled Copy - Refer to Ampcontrol Website for Latest Version
APPROVED FOR EXTERNAL DISTRIBUTION
PROPERTY OF AMPCONTROL PTY LTD
NOT TO
BE REPRODUCED IN PART
Register
Description
R/W
Detail
Format
SCADA*
54
Last t90 result in 0.1s (e.g.
101 = 10.1s)
Unsigned Int
55
Detector last t90 test date
(in Ampcontrol date format)
Time in seconds since
01-01-2000 00:00
32 bit
Unsigned Int
56
Detector last t90 test date
(in Ampcontrol date format)
57
Time in seconds cal cup left
on last
increments while cal cup
on, doesn't roll over past
FFFF
Unsigned Int
58
Detector last Cal Cup
applied date (in Ampcontrol
date format)
Time in seconds since
01-01-2000 00:00
32 bit
Unsigned Int
59
Detector last Cal Cup
applied date (in Ampcontrol
date format)
60
Time in seconds last spent
in telemetry test
increments during active
test
Unsigned Int
61
Detector last telemetry test
date (in Ampcontrol date
format)
Time in seconds since
01-01-2000 00:00
32 bit
Unsigned Int
62
Detector last telemetry test
date (in Ampcontrol date
format)
63
Detector Last in-situ
adjustment date
(Ampcontrol date format)
Time in seconds since
01-01-2000 00:00
32 bit
Unsigned Int
64
Detector Last in-situ
adjustment date
(Ampcontrol date format)
65
Detector coms error count
clear on sensor power
up, accumulate and hold
at FFFF
Signed Int
66
Detector hours of run time
since build/overhaul
max out at FFFF, don't
roll over
Unsigned Int
67
Display hours of run time
since build/overhaul
max out at FFFF, don't
roll over
Unsigned Int
68
Time in seconds last spent
in bypass
increments during active
bypass
Unsigned Int
69
Display bus voltage
Millivolts (mV)
Signed Int
70
4-20mA conversion value
µA. Intended 4-20mA
analog signal value
Unsigned Int