36
Andover Controls
SPECIFICATIONS
ELECTRICAL
Power Consumption:
0.7 Watt at 24VDC max.; normally provided by
Continuum
power
supply module.
Overload Protection:
0.5A resettable fuse with transient voltage suppressor (TVS) and
reverse polarity protection.
INPUTS
Number of Inputs:
6 Digital AC voltage inputs
Input Protection:
2500V isolation on each input
Each input has a 270V MOV.
Input Connections:
Two-piece, 13-position removable terminal block
DI-6-AC DI-6-AC-HV
Input Range:
20-132 Vrms 90-250 Vrms
Input Current:
5 mA max. 2 mA max.
DI-6-AC DI-6-AC-HV
AC Voltage “ON” Threshold:
16 Vrms 75 Vrms
(Above this voltage is considered “ON”)
AC Voltage “OFF” Threshold:
8 Vrms 30 Vrms
(Below this voltage is considered “OFF”)
Input Resistance
(±5%): 30KΩ 200KΩ
Maximum Turn ON Time:
20 mS 20 mS
Maximum Turn OFF Time:
60 mS 60 mS
DC Input Voltage Range:
20-132V 90-250V
DC Input Current:
5mA max. 2mA max.
DC Voltage “ON” Threshold:
20V 90V
(Above this voltage is considered “ON”)
DC Voltage “OFF” Threshold:
12V 45V
(Below this voltage is considered “OFF”)
DI-6-AC
Technical Manuals Online! - http://www.tech-man.com