Continuum I/O System Reference
75
I/O Connections
The actual output connections are located on a thirteen-position removable screw
terminal connector located at the bottom of the module. Output wires should enter from
either the top or bottom wiring troughs, and should come from the right side of the rack
(by convention).
The outputs are labeled OUT1 I, OUT1 V, OUT1 GND, and so forth. Each output
presents two ways of connecting, resulting in a current output of OUT1 I and OUT1 GND,
and a voltage output between OUT1 V and OUT1 GND.
The diagram below indicates where each output number is located in the terminal block.
Shield/Earth Ground
1.
OUT1 I
2.
OUT1 V
3.
OUT1 GND
4.
OUT2 I
5.
OUT2 V
6.
OUT2 GND
7.
OUT3 I
8.
OUT3 V
9.
OUT3 GND
10.
OUT4 I
11.
OUT4 V
12.
OUT4 GND
USE COPPER CONDUCTORS ONLY
10 11 12
13 14 15
1-DOOR
OUT2
DIGITAL OUTPUTS
CONTACT RATING:
12
3
4
56
7
8
+
G
DC
A
T
A
/
1
L
K
/
0
N
D
V
L
E
D
A
U
X
O
O
R
R
E
X
READER
SUPERVISED
INPUTS(0-5V)
+ 5V, 100mA
+ 12V, 180mA
1-DOOR
ON
OFF
AUTO
OUT 2
ON
OFF
AUTO
D
9
R
E
T
1
23
READER
POWER
COMMISSION
RESET
POWER
COMM
STATUS
OVERRIDE
AO-4
OUT1
123456789101112
ANALOG OUTPUTS
CURRENT OUTPUT: 0 - 20mA, 650 OHMS MAX.
VOLTAGE OUTPUT: 0 - 10V, 2K OHMS MIN.
ADJUST
ADJUST ADJUST ADJUST
I
V
GND
OUT2
OUT3
OUT4
OUT1
MANUAL
OFF
AUTO
OUT2
OUT3 OUT4
I
V
GND
I
V
GND
I
V
GND
USE COPPER CONDUCTORS ONLY
MANUAL
OFF
AUTO
MANUAL
OFF
AUTO
MANUAL
OFF
AUTO
MANUAL
AO-4-8