Continuum I/O System Reference
37
I/O Connections
The actual input connections are located on a twelve-position removable screw terminal
connector located at the bottom of the module. Input wires should enter from either the
top or bottom wiring troughs, and should come from the left side of the rack (by
convention).
The inputs are labeled IN1, IN2, IN3, and so forth. Each pair of terminals corresponds to
one input. With both AC and DC signals there is no polarity to observe during connection.
The diagram below indicates where each input number is located in the terminal block.
Shield/Earth Ground
1.
IN 1
2.
IN 1
3.
IN 2
4.
IN 2
5.
IN 3
6.
IN 3
7.
IN 4
8.
IN 4
9.
IN 5
10.
IN 5
11.
IN 6
12.
IN 6
DI-6-AC
USE COPPER CONDUCTORS ONLY
10 11 12
13 14 15
1-DOOR
OUT2
DIGITAL OUTPUTS
CONTACT RATING:
24VAC/DC, 5A
12
3
4
56
7
8
+
G
DC
A
T
A
/
1
L
K
/
0
N
D
V
L
E
D
A
U
X
O
O
R
R
E
X
READER
SUPERVISED
INPUTS(0-5V)
+ 5V, 100mA
+ 12V, 180mA
1-DOOR
ON
OFF
AUTO
OUT 2
ON
OFF
AUTO
D
9
R
E
T
1
23
READER
POWER
1
2
3
4
INPUT
5
6
INPUT
DI-6
POWER
COMM
STATUS
COMMISSION
RESET
123456789101112
IN1
IN2 IN3 IN4 IN5 IN6
DIGITAL INPUTS
USE COPPER CONDUCTORS ONLY
DI-6-AC DI-6-AC-HV
VOLTAGE RANGE(VAC) 50/60 HZ 20 - 132 90 - 280
INPUT CURRENT(mA) 0.4 - 9.0 0.4 - 3.0
WARNING:
AVERTISSEMENT:
CAUTION:
MORE THAN ONE DISCONNECT MAY BE
REQUIRED TO DE-ENERGIZE THIS EQUIPMENT.
HAUTE TENSION A L'INTERIEUR-DANGER
POUR LES PERSONNES NON-QUALIFIER.
HIGH VOLTAGE INSIDE-DANGEROUS TO
UNQUALIFIED PERSONS.