Page 6 IPC2 Power Charger User Manual, Part No 13130 issue 4
SPECIFICATIONS
Model range & part numbers
90165 - 12 volt 40 amp, 230VAC
90166 - 12 volt 40 amp, 110VAC
90167 - 24 volt 20 amp, 230VAC
90168 - 24 volt 20 amp, 110VAC
90173 - 24 volt 15 amp, 230VAC
90174 - 24 volt 15 amp, 110VAC
90175 - 24 volt 15 amp, with auxiliary 12V, 230VAC
90176 - 24 volt 15 amp, with auxiliary 12V, 110VAC
90177 - 24 volt 20 amp, with auxiliary 12V, 230VAC
90178 - 24 volt 20 amp, with auxiliary 12V, 110VAC
90181 - 12 volt 30 amp, 230VAC
90182 - 12 volt 30 amp, 110VAC
Input specifications
Input voltage range:
230 volt models: 200 to 264VAC continuous, 275VAC intermittent.
110 volt models: 95 to 121VAC continuous, 126VAC intermittent.
Input frequency range: 45 to 66Hz
Inrush current:
230 volt models: 85 amps peak, 1.2 milliseconds
total inrush 0.1 amp-seconds
110 volt models: 39 amps peak, 5.2 milliseconds
total inrush 0.2 amp-seconds
Insulation class I; protective earth required, supplied via mains input cable.
Output specifications
Output voltage:
12 volt models:
Float voltage 13.7VDC at 20° C
Boost voltage 14.2VDC at 20° C
Temperature coefficient -24mV/degC
24 volt models:
Float voltage 27.4VDC at 20° C
Boost voltage 28.6VDC at 20° C
Temperature coefficient -47mV/degC
Aux 12volt output:
Float voltage 13.8VDC
Charging current 1.5 amps (typical)
Battery sensing threshold
12 volt models: 4.0 volts
24 volt models: 4.0 volts
The battery voltage must be higher than this threshold for charging to commence.
Climatic specifications:
Operating temperature range:
Full output power: -5°C to +30°C
Reduced output power +30° to +45°C
(IPC2 is self limiting)