16 Installation and Quick Start
Quick Configuration
2. Use Ping with a size of 113 bytes to assign the IP address
defined by the ARP command. For the IP address
defined in step 1, use one of the following commands:
Windows command format:
ping 156.205.14.141 -l 113
LINUX command format:
ping 156.205.14.141 -s 113
3. Use Telnet to access the Management Card at its newly
assigned IP address. For example:
telnet 156.205.14.141
4. Use apc for both user name and password.
5. See “Control console” on page 16 to finish the
configuration.
Control console
After you log on at the control console, as described in “Local
access to the control console” on page 15 or “Remote access to
the control console” on page 15:
1. Choose Network from the Control Console menu.
2. Choose TCP/IP
from the Network menu.
3. If you are not using a BOOTP or DHCP server to
configure the TCP/IP settings, select the Boot Mode
menu and then select Manual.
4. Set the System
IP, Subnet Mask, and Default Gateway
address values. (Changes take effect when you log off.)
5. Press
ENTER to return to the TCP/IP menu.
6. Press
CTRL+C to exit to the Control Console menu.
7. Log out (option 4 in the Control Console menu).
Note
If you disconnected a cable during the
procedure described in “Local access to the
control console” on page 15, reconnect that
cable and restart the associated service.

Other manuals for APC AP9617

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC AP9617 and is the answer not in the manual?

APC AP9617 Specifications

General IconGeneral
TypeNetwork Management Card
ModelAP9617
Data Link ProtocolEthernet, Fast Ethernet
Network Ports Qty1
Network ProtocolsTCP/IP, HTTP, HTTPS, SNMP, Telnet, SSH
ManagementSNMP
CompatibilitySmart-UPS
Remote Management ProtocolSNMP, HTTP, HTTPS, Telnet, SSH
SecuritySSL, SSH
Operating Temperature0 to 45 °C
Storage Temperature-15 to 65 °C
Humidity0 to 95% non-condensing
PortsRJ-45 Ethernet