APC Symmetra Rack Mount
Uninterruptible Power Supply
PDU Installation Manual
990-7136 Revision 1
1. Introduction
These instructions describe how to safely install an APC Symmetra Rack Mount PDU.
Carefully read these instructions in their entirety before continuing.
WARNING!
Only qualified service personnel or electricians may perform the following procedure. The electrical terminals exposed in the following procedures will be energized if the UPS is on or plugged in.
Make sure the UPS is both unplugged and off. Make sure that the UPS’ DC battery system has been discharged. Refer to Users Manual for instructions.
2. Required Materials and Tools
NOTE: Wiring codes and requirements differ from area to area. Be sure to conform to all local electrical requirements when installing and wiring this UPS.
The following tools are required for installation:
#2 Phillips Screwdriver
3. Installation
This section provides step-by-step instructions for removing and installing a PDU to a Symmetra Rack Mount UPS. The images depict a typical PDU installation.
3.1 Remove Existing Panel
1. Remove the 4 screws that retain the PDU panel as shown in Fig. 3.1 and set
aside.
2. Disconnect the two connectors by squeezing the two ears on the connector and
gently pulling it from its mating connector. Set aside the removed PDU.
1
2
Figure 3.1 Remove Existing PDU
3.2 Install New Panel
3. Remove new PDU form it’s box and install new PDU by first reconnecting the
connectors as shown in Fig. 3.2
4. Check fit of wiring by installing panel without securing screws. Adjust wires as
needed. Reattach the 4 screws and tighten.
3
4
Figure 3.2 Install New PDU

Other manuals for APC PDU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the APC PDU and is the answer not in the manual?

APC PDU Specifications

General IconGeneral
Input Frequency50/60 Hz
DimensionsVaries by model
WeightVaries by model
Product TypePDU
Form FactorRackmount
Input Voltage100-240V
Output Voltage100-240V
Output ConnectionsIEC C13, IEC C19
Input Connection TypeIEC 60320 C14, IEC 60320 C20
Maximum Load Current16A, 20A, 30A
Number of Outlets8, 12, 24
MountingRackmount
Rack Height1U, 2U
Operating Temperature0°C to 50°C
Operating Humidity5% to 95% non-condensing