These settings are also for the replacement of the vintage Signature 2012
and earlier ( Part # 17P549-03 ) with the 2013 ( 100-202A ) control board
Setting up the unit So the Display shows the Water Temp. in Fahrenheit instead of Celsius
1. Hold down the “Up” and “Down” arrows for approximately 10 seconds
2. Unit will display “ F – C “ , this is the calibration for Fahrenheit or Celsius
3. Press the “Up” Arrow to Select “ *F “
4. Once the selection is made wait 10 seconds for the display to time out and go back to the normal
display. The unit should now display the water Temp. in Fahrenheit.
Setting up the Unit for cooling function on A Heat / Cool Model
1. Hold down the “Up” and “Down” arrows for approximately 10 seconds
2. Unit will display “ F – C “ , this is the calibration for Fahrenheit or Celsius
3. Press the “Hand” button until it reads the “ P - C “ on the display
4. Press the “Up” arrow twice so that the Display reads “ EnA
5. Once the selection is made wait 10 seconds for the display to time out and go back to the normal
display. Now press the “ Hand “ button until you the display reads “PHC “.
6. Press the “ Up” or “Down” arrow to select either “P_H” for heating or “P_C” for cooling.
Setting the Filter timer function to Disabled on the Heatpump
1. It is important that the “ FiL” setting is set to “DIS” for disabled. If the “FiL” setting is enabled follow
these steps
2. Hold down the “Up” and “Down” arrows for approximately 10 seconds
3. Unit will display “ F – C “ , this is the calibration for Fahrenheit or Celsius
4. Press the “Hand” button until it reads the “ FiL”
5. Press the “Down” arrow until it reads “DIS”
6. Once the selection is made wait 10 seconds for the display to time out and go back to the normal
display.
Calibrations and Settings for ACT
Signature Series and XL Series
Manufactured from 2013 through 2-26-15
with Serial number 1500379 and lower
Models :
ACT750,
ACT1100,
ACT1250,
ACT1500,
ACT1750,
And All H/C Variants
THE POOL HEATING SOLUTION
Question and Answer IconNeed help?

Do you have a question about the Aqua Comfort ACT1500 and is the answer not in the manual?

Aqua Comfort ACT1500 Specifications

General IconGeneral
BrandAqua Comfort
ModelACT1500
CategoryHeat Pump
LanguageEnglish

Summary

Calibrations and Settings for ACT Signature and XL Series

Set Water Temperature to Fahrenheit

Configure the unit to display water temperature in Fahrenheit instead of Celsius.

Set Cooling Function on Heat/Cool Models

Enable the cooling function for models that support both heating and cooling.

Disable Heat Pump Filter Timer

Set the filter timer function to disabled on the heat pump.

Heat Pump Calibration and Adjustment Procedures

Calibrate Water Temperature Display

Calibrate the displayed water temperature to match the actual temperature.

Adjust Deadband (Temperature Off Setting)

Adjust the deadband setting to control how long the unit stays off after reaching setpoint.

Select Defrost Mode

Select the defrost mode: air defrost ('Alr') or reversing valve defrost ('rEC').

Bypass 5-Minute Delay

Bypass the heat pump's standard 5-minute start delay for the compressor or fan.