21
8.6.1.2 When the compressor is switched off and restarts again to operate, restarting period is 3 min and 30 s.
8.6.2 Defrosting protection mode (Electrical defrosting) for DADOS 9 & 13.
This protection prevents ice formation on the heat exchanger.
The protection is activated if the fan coil temperature is 1°C and after 15 minutes operation.
If temperature is 6°C defrosting mode will be off.
Defrosting protection mode (two way valve defrosting) for DADOS XL
If the coil temperature detected is 0°C continuously for 5 min, the prevention deicing pipeline will start.
When temperature will be 2°c then the system will exit the defrosting mode.
If the coil temperature detected is -3°C continuously for 10 min, the prevention deicing pipeline will start.
When temperature will be 2°c then the system will exit the defrosting mode.