7-7 Fan motor works normally but the compressor does not operate
Check hardness
and continuity. Is the
relay compressor
coil (PR white cable)
power supplied ?
YES
Replace the relay NO Check if relay YES Is the thermostat in NO Adjust thermostat
(PR) contects are closed the right position ? position
YES YES
Replace klixon (ORL) YES Check compressor Is room tempera - NO The unit cannot
klixon contacts (ORL) ture over 15 °C ? operate below
Are they open ?
15 °C
NO YES
Replace the NO Check the capaci - Check the sensor NO Replace the
capacitor (C) tor capacity (C) continuity (TH2) sensor (TH2)
through 9-10
electronic control
YES (CE) terminal
blocks
YES
Replace the NO Check the com - Check electronic
compressor pressor winding control (CE)
continuity