16
GB
start-up
PARAMETER 1100 = 4
[Thermostat]
LN LN
IN 1 IN 2
OUT 1
LN
OUT 2
LN
230V OUT 3
IN 3
BUS
BT
In this mode, the device functions as a ge-
neric thermostat between a sensor con-
nected to input IN1 and a setpoint (target)
temperature.
If the IN1 temperature exceeds the setpoint
value (set via parameter 1130) by a cer-
tain number of degrees (set via parameter
1131), output OUT1 is activated.
Par. Description Range
1110 IN1 temperature
reading
-20..150°C
1130 Temperature set 0..130°C
1131 Hysteresis 0..30°C
230 V PUMP
SOLAR HEATING SYSTEM INTER-
FACE BOILER
230 V PUMP SENSOR
SOLAR HEATING
SYSTEM ZONES
BOILER
PARAMETER 1100 = 5
[Timed output, in conjunction with a system
interface]
LN LN
IN 1 IN 2
OUT 1
LN
OUT 2
LN
230V OUT 3
IN 3
BUS
BT
In this mode, output OUT1 is powered in
line with a programmed schedule, which
can be set using the system interface (in-
dispensable for managing this function) as
follows:
Press ok > Complete menu > Hot water
settings > Free programming > Auxiliary
timer
Application example:
- by connecting a recirculation pump to
OUT1, it will be possible to operate it on a
timed basis (e.g. On in the daytime, Off at
night).