COMMISSIONING
Operation 4 - Checking the CO2 at minimum gas ow
With the Test function active, press the 2
button to select the
icom
and . The boiler is forced to the minimum power.
Wait 1 minute for the boiler to stabilise before carrying out the
combustion analyses.
If the
CO2 value (%) read
differs by 0.5 % from the
value found, then adjust
the gas valve following the
instructions below, otherwise
move directly onto operation
5.
Adjusting the gas valve to
minimum gas ow
Remove
cap and adjust screw 2 by turning anti-clockwise in
increments to reduce the CO2 level. Wait 1 minute after each
adjustment for the CO2 value to stabilise.
WARNING! this adjustment is sensitive: a rotation of a 1 turn
corresponds to 0.2% of CO2.
If the value measured corresponds to the value given in the
table, adjustment is complete, otherwise start the setting
procedure again.
Attention! If the value of the CO2 at the minum power has
been changed, it is necessary repet the adjusting at maximum
gas ow.
Operation 5 - Ending the adjustment
Exit cleaning mode by pressing RESET.
Stop the draw-off.
Verify and repair any leaks of gas.
Ret the front panel to the device.
Ret the blanking cover at combustion test point.
21.4
3.4
menu 2 - Boiler parameters
submenu 3 - parameter 1 Maximum Heating Power adjustment
submenu 2 - parameter 0
Soft light Ignition
submenu 3 - parameter 5 Heating ignition delay
Maximum Heating Power adjustment
The maximum heating power can be adjusted to between the
maximum power allowed by the boiler and the minimum power).
The display shows the value between 100% (“100” on the
display) and 0% (“0”) of this interval.
To check the maximum heating power, access menu 2/sub menu
3/parameter 1, check the value and, if necessary, modify it as
indicated in the Gas Regulation table below. (See page 40 for
more details).
Checking slow ignition power
The soft light can be adjusted between the maximum power
(shown on the display as “100”, i.e. 100%) and the minimum
power (shown on the display as “1”, i.e. 1%).
To check the slow ignition power, access menu 2/sub menu 2/
parameter 0.
Heating ignition delay adjustment
This parameter – menu 2/sub menu 3/parameter 5 - can be used
to manually (0) or automatically (1) set the delay time before the
subsequent reignition of the burner after it has switched off on
reaching the desired temperature in central heating mode.
By selecting manual, it is possible to set the delay in minutes
using the successive parameter (menu 2/sub menu 3/parameter
6), to a time between 0 and 7 minutes.
Automatic selection means that the boiler will establish the
delay time based on the set-point temperature