Power supplies of the HYBRID MODULE and the outdoor units are to be respectively connected to a Residual Current operated Circuit-
Breaker (RCCB) with threshold of 30mA. For inverter driven units (outdoor unit), It is advisable the use of type B residual current device
for 3Ph power supplies and type B or F for 1Ph power supplies (depending on the electrical system to which it is connected). For the
units without inverter, (HYBRID MODULE) a type A Residual current device is sucient. The type of connection must in any case be
carried out in a workmanlike manner by qualified personnel in compliance with the national regulations in force.
HYBRID MODULE
Electrical supply V - ph - Hz 230 - 1 - 50
Admitted voltages field V 196 ÷ 253
Rated power input W 10
Nominal current/phase A 40
Cutout - Circuit Breaker size (*)
A 2- C type ( 6A max. )
Dierential Circuit Breaker size (RCCB)
mA 30
Power Supply Cable
Reference H05V2V2-F
Cable section 3x0.75
Max diameter [mm] 6.3
Wiring signal HV IN 1,2,3
mm
2
1,5