18
GB
MENU PARAMETER DESCRIPTION
RANGE
VALUE
Engineer
Heating circuit 1
(ZONE 1)
710 Heating circuit 1 Comfort setpoint 16-35°C 20°C
712 Heating circuit 1 Reduced setpoint 16-35°C 16°C
714
Heating circuit 1
Frost protection setpoint
4-16°C 10°C
720
Heating circuit 1
Heating curve slope
0.10-4.00 1.50
721
Heating circuit 1
Heating curve displacement
-4.5 - 4.5°C 0.0
730
Heating circuit 1
Summer/winter heating limit
- - -°C - 30.0°C
(--- = deactivated)
20.0°C
740
Heating circuit 1
Flow temp setpoint min
8°C at par. 741 8°C
741
Heating circuit 1
Flow temp setpoint max
par. 740 at 95°C 80°C
Engineer
Heating circuit 2
(ZONE 2, only if
active)
1010 Heating circuit 2 Comfort setpoint 16-35°C 20°C
1012 Heating circuit 2 Reduced setpoint 16-35°C 16°C
1014
Heating circuit 2
Frost protection setpoint
4-16°C 10°C
1020
Heating circuit 2
Heating curve slope
0.10-4.00 1.50
1021
Heating circuit 2
Heating curve displacement
-4.5 - 4.5°C 0.0
1030
Heating circuit 2
Summer/winter heating limit
- - -°C - 30.0°C
(--- = deactivated)
20.0°C
1040
Heating circuit 2
Flow temp setpoint min
8°C at par. 1041 8°C
1041
Heating circuit 2
Flow temp setpoint max
par. 1041 at 95°C 80°C
Engineer
3/P heating circuit
(ZONE 3, only if
parameter 5890 is
active)
1310 Heating circuit 2 Comfort set-point 16-35°C 20°C
1312 Heating circuit 3 Reduced set-point 16-35°C 16°C
1314
Heating circuit 3
Frost protection setpoint
4-16°C
1320
Heating circuit 3
Heating curve slope
0.10-4.00 1.50
1321
Heating circuit 3
Heating curve displacement
-4.5 - 4.5°C 0.0
1330
Heating circuit 3
Summer/winter heating limit
- - -°C - 30.0°C
(--- = deactivated)
20.0°C
1340
Heating circuit 3
Flow temp setpoint min
8°C at par. 1341 8°C
1341
Heating circuit 3
Flow temp setpoint max
par. 741 at 95°C 80°C
Engineer
DHW
(Storage cylinder)
1610 Nominal setpoint par. 1612 at 65°C 55°C
1612 Reduced setpoint from 8°C par. 1610 40°C
Engineer
1640 Legionella function
- Off
- Periodically
(x =
days: par. 1641)
- Fixed weekday
(
par. 1642)
OFF
1641
Legionella funct periodically
(parameter 1640: periodic)
3 days 3 days
1642
Legionella funct weekday
(parameter 1640: fi xed day)
Monday... Sunday Monday
PARAMETER SETTING