8
GB
ZONE 1 ZONE 2 ZONE 3
QAA75 Room thermostat Room thermostat
Parameter 40 Internal unit 1 Parameter 5950
Optg mode
changeover HC2
Parameter 5960
Optg mode
changeover HCP
Parameter 42 Heating circuit 1 Parameter 5951 NC Parameter 5961 NC
Electrical connection CL+ / CL- Electrical connection H1 / M Electrical connection H3 / M
Room thermostat QAA75 Room thermostat
Parameter 5950
Optg mode
changeover HC1
Parameter 40 Internal unit 2 Parameter 5960
Optg mode
changeover HCP
Parameter 5951 NC Parameter 42 Heating circuit 2 Parameter 5961 NC
Electrical connection H1 / M Electrical connection CL+ / CL- Electrical connection H3 / M
Room thermostat Room thermostat QAA75
Parameter 5950
Optg mode
changeover HC1
Parameter 5960
Optg mode
changeover HC2
Parameter 40 Internal unit P
Parameter 5951 NC Parameter 5961 NC Parameter 42 Heating circuit 3
Electrical connection H1 / M Electrical connection H3 / M Electrical connection CL+ / CL-
QAA75 QAA75 Room thermostat
Parameter 40 Internal unit 1 Parameter 40 Internal unit 2 Parameter 5950
Optg mode
changeover HCP
Parameter 42 Heating circuit 1 Parameter 42 Heating circuit 2 Parameter 5951 NC
Electrical connection CL+ / CL- Electrical connection CL+ / CL- Electrical connection H1 / M
QAA75 Room thermostat QAA75
Parameter 40 Internal unit 1 Parameter 5950
Optg mode
changeover HC2
Parameter 40 Internal unit P
Parameter 42 Heating circuit 1 Parameter 5951 NC Parameter 42 Heating circuit 3
Electrical connection CL+ / CL- Electrical connection H1 / M Electrical connection CL+ / CL-
Room thermostat QAA75 QAA75
Parameter 5950
Optg mode
changeover HC1
Parameter 40 Internal unit 2 Parameter 40 Internal unit P
Parameter 5951 NC Parameter 42 Heating circuit 2 Parameter 42 Heating circuit 3
Electrical connection H1 / M Electrical connection CL+ / CL- Electrical connection CL+ / CL-
QAA75 QAA75 QAA75
Parameter 40 Internal unit 1 Parameter 40 Internal unit 2 Parameter 40 Internal unit P
Parameter 42 Heating circuit 1 Parameter 42 Heating circuit 2 Parameter 42 Heating circuit 3
Electrical connection CL+ / CL- Electrical connection CL+ / CL- Electrical connection CL+ / CL-
NOTE:
. Parameters 40 and 42 visible on remote control QAA 75
. Combinations possible even with 1 or 2 zones
. In systems with 3 zones it is necessary to use remote control QAA 75 for managing a zone.
MANAGEMENT OF ZONE CONTROL DEVICES