© 2020 UTC Fire & Security. All rights reserved. 1 / 4 P/N 20-8030-501-0000-06 • ISS 05MAR20
D1112-2
DM2010 Manual Call Point Installation Sheet
EN IT
1
2
EN: Installation Sheet
Description
The DM2010 manual call point is designed for use in Aritech
analogue addressable fire alarm systems and include models
for indoor and outdoor use.
Installation
Caution: This product must be installed by qualified personnel
adhering to the CEN/TS 54-14 standard and any other
applicable local authority laws.
Electrical connections
Connect to the DM2010 connection block (Figure
2) as follows:
1. Line in (positive)
2. Line out (positive)
3. Line in (negative)
4. Line out (negative)
Addressing
Use the DIP switch (Figure 1) to allocate a device address
from 1 to 128 (see page 3).
Maintenance
Basic maintenance consists of a yearly inspection. Do not
modify internal wiring or circuitry.
Specifications
Voltage
17 to 28 VDC
Current
consumption
Standby
Alarm
max. 250 ųA
max. 2.5 mA
Cable size
Minimum
Maximum
0.8 mm2
2.5 mm2
IP rating
DM2010, DM2010-18
DM2010E, DM2010E-18
IP24D
IP67
Operating temperature
DM2010, DM2010-18
DM2010E, DM2010E-18
10°C to +55°C
25°C to +70°C
Storage temperature
DM2010, DM2010-18
DM2010E, DM2010E-18
10°C to +70°C
25°C to +70°C
Relative humidity
10% to 95% noncondensing
Dimensions (W × H × D)
DM2010, DM2010-18
DM2010E, DM2010E-18
89 x 93 x 27.5 mm [1]
97.5 x 93 x 27.5 mm [1]
Weight
DM2010, DM2010-18
DM2010E, DM2010E-18
180 g
350 g
[1] Excluding surface mount
Question and Answer IconNeed help?

Do you have a question about the Aritech DM2010 and is the answer not in the manual?

Aritech DM2010 Specifications

General IconGeneral
Number of Sounders2
TypeConventional Fire Alarm Panel
Input Voltage12-24V DC
Relative Humidity95% non-condensing
Weight2.5kg

Summary

Installation and Configuration

Product Description

Details the DM2010 manual call point for Aritech analogue addressable fire alarm systems.

Installation Requirements

Highlights the need for qualified personnel and adherence to safety standards and local laws.

Electrical Connections Guide

Provides instructions for connecting the DM2010 to the DM2010 connection block.

Device Addressing

Explains using the DIP switch to allocate a device address from 1 to 128.

Maintenance and Specifications

Maintenance Procedures

Outlines basic yearly inspection requirements and prohibits internal modification of wiring or circuitry.

Technical Specifications Overview

Lists key electrical, environmental, and physical characteristics of the DM2010 units.