EasyManua.ls Logo

Aritech ISM-95 User Manual

Aritech ISM-95
6 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Page #1 background imageLoading...
Page #1 background image
© 2011 UTC Fire & Security. All rights reserved. 1 / 2 P/N 3101877 • REV 1.0 • ISS 14JUN11
ISM-95 Isolator Module Installation Sheet
EN DE ES FR NL PL PT RU
1
EN: Installation Sheet
Description
The ISM-95 Isolator Module provides short circuit protection for
an addressable loop. When a short circuit is detected on the
fire panel loop on either side of the isolator, that side will be
isolated and the yellow "isolated" LED will turn on. When the
short clears, the isolator automatically resets and reconnects
the loop.
If required, one additional device can be connected to a short
spur connection. A device connected to the short spur
connection will continue to receive power from the one side of
the loop and remain operational in case of a short circuit on the
loop. A short circuit on the spur will short circuit both sides of
the loop (bypass the isolator).
Installation
The ISM-95 is designed for use in dry environments. The
module is supplied in an IP55 enclosure. Mount the enclosure
at a suitable location, and then connect the field wiring in
accordance with “Connections.”
Connections
The incoming addressable loop can be connected to either set
of Loop + and Loop – terminals (1 and 2 or 5 and 6) shown in
Figure 1.
The outgoing addressable loop is connected to the remaining
set of Loop + and Loop – terminals (5 and 6 or 1 and 2). Do not
mix connections between the incoming and outgoing.
If an additional device is to be used on a spur, it must be
connected to terminals S+ and S– shown in Figure 1.
Figure 1 shows connections for the ISM-95.
1. Loop +
2. Loop
3. Spur connection+ (S+)
4. Spur connection– (S–)
5. Loop +
6. Loop
7. Isolator LED
Maintenance
The only maintenance required is a yearly inspection. Do not
modify the internal wiring or circuitry.
Specifications
Operating temperature 0 to +50°C
Operating voltage 24 VDC
Switching voltage
(normal to isolated)
13.8V
IP rating IP55
Dimensions (W × H × D) 43 × 89 × 37 mm
Weight 147 g
Question and Answer IconNeed help?

Do you have a question about the Aritech ISM-95 and is the answer not in the manual?

Aritech ISM-95 Specifications

General IconGeneral
ModelISM-95
ManufacturerAritech
Number of Zones8
Operating Temperature-10°C to +55°C
Weight1.5kg
Zone TypesWired

Summary

Module Description and Functionality

Product Description

Explains the ISM-95 Isolator Module's role in short circuit protection and LED indicator behavior.

Spur Connection Usage

Details how an additional device on a spur connection interacts with loop faults.

Installation and Connections

Installation Environment

Specifies that the ISM-95 is designed for dry environments and requires IP55 enclosure mounting.

Loop Wiring

Guides on connecting incoming and outgoing addressable loops to specific terminals.

Spur Connection Wiring

Instructs on connecting an additional device to the S+ and S- spur terminals.

Maintenance and Specifications

Maintenance Requirements

States that only a yearly inspection is required, prohibiting internal modifications.

Technical Specifications

Lists key parameters: operating temperature, voltage, switching voltage, IP rating, dimensions, and weight.

Related product manuals