Notes: In one LCD interface, only one special character can be added.
4.2 Application Examples of HMI
Note
£
º
This is a water supply system.
1£® The water supply system diagram is as follows:
Fig. 4.9
2. Description
a. We use a SR-12MRD to compare the Pressure 1 and 7V, if P1<7v, then
start the pump #1; if P1<3v, then start the pump #2; if P1<1v for more than 5
minutes, then start the voice alarm. Connect P1 to I0(I0¡XI7) are analog input)
b. SA is a Manual/Auto switch£¬connected to I4 and I5.
c. When you choose SA as manual operation, there are two function keys in
the program, V: AF1 will control the pump #1, and V: AF2 will control
pump #2.
d. When you choose SA as Auto operation, the pressure comparing
instructions B0, B1 and B6 will work; the parameters of B0, B1 and B6 are
as follows: