automatically and broadcast-Please enter the password for confirmation, then the
user enter the SR password.
A. If the entered password is correct, SR will then broadcast-Correct password.
Please enter the control code to control. Then the user can control the
equipment by the use of the telephone.
B. If the entered password is not correct, the SR will broadcast-Wrong password.
Please re-enter. Then the system will repeatedly broadcast-Please enter the
password for confirmation.
Step III:
When SR dials an external telephone number, it will broadcast the pre-set
message such as section 5-Emergency. Gas leakage. Together with section
4-Emergency. Please enter the password to control.
A. When the user enters the correct password, the voice system will broadcast
section 2-Correct password. Please enter the control code to control and then
repeatedly broadcast section 5-Emergency. Gas leakage. At this time the user
can real-time control the equipment by the use of the telephone.
B. When the user enters a wrong password, the voice system will broadcast section
3-Wrong password. Please re-enter. And then it will broadcast section 4 and
section 5 repeatedly.
Notes:
1. SR dialing an external telephone, if there is no answer or a password is not
input within 40 seconds of the connection, the SR voice system will stop
dialing and cease to broadcast the voice message. The SR voice system will
then redial automatically every 40 seconds.
2. User must enter a * before entering the password. The broadcasting will
then stop and the user should enter a four-digit password within 9 seconds.
If the user fails to enter the password, the SR voice system will rebroadcast
the prompt voice. The user must then enter * first and then enter the
password. If the user needs to enter the password again the procedure needs
to be repeated. That is to say that every time user entering the password, he
must enter a * first and enter a four-digit password within 9 seconds after
the stop of the voice.
3. When the user has entered the correct password, the voice system will
broadcast section 2-Correct password. Please enter the control code to
control and then the user can do the following operation. If the password is
wrong, the voice system will broadcast section 3-Wrong password. Please
re-enter. The user can only enter the wrong password three times. If the user
enters the wrong password for the fourth time, SR will hang up the
telephone and stop broadcasting. And the system will then return to the
main system. If the alarm status still exists, the voice system will dial
automatically, for alarm purposes, every 40 seconds.
4. When the alarm status exists, SR voice module will broadcast the alarm
voice repeatedly. It can be stopped by the use of the control function within
the program.
5. After SR voice module has dialed if the user does not switch-off the alarm
ON/OFF switch via the anti-control function i.e., the status of alarm is not