Voltage Range
Zone Type 14
P 125 E (Z1-8) E
0.0—0.70V Low Zone Tamper
0.70—1.40V SEALED
1.40—2.30V Low Zone Alarm
A
B
C
E 2.80—3.30V High+Low Alarm
D 2.30—2.80V High Zone Alarm
F 3.30—5.0V High Zone Tamper
Alarm
Contacts N/C
4K7
Z1-8
COM
TYPE 14: Zone Doubling with Tampers.
Low Zone = PIR-A (N/C)
High Zone = PIR-B (N/C)
2K2
PIR-A
Tamper
Contacts
Alarm
Contacts N/C
8K2
PIR-B
Tamper
Contacts
Zone Doubling Type 14 (with tampers)
Voltage Range
Zone Type 14
P 125 E (Z1-8) E
0.0—0.70V Low Zone Tamper
0.70—1.40V High Zone Alarm
1.40—2.30V High+Low Alarm
A
B
C
E 2.80—3.30V Low Zone Alarm
D 2.30—2.80V SEALED
F 3.30—5.0V High Zone Tamper
Alarm
Contacts N/C
4K7
Z1-8
COM
TYPE 14: Zone Doubling with Tampers.
Low Zone = PIR-A (N/C)
High Zone = Smoke Detector (N/O)*
2K2
PIR
Tamper
Contacts
Alarm
Contacts N/O
8K2
Smoke
Voltage Range
Zone Type 14
P 125 E (Z1-8) E
0.0—0.70V Low Zone Tamper
0.70—1.40V High+Low Alarm
1.40—2.30V High Zone Alarm
A
B
C
E 2.80—3.30V SEALED
D 2.30—2.80V Low Zone Alarm
F 3.30—5.0V High Zone Tamper
Alarm
Contacts N/C
8K2
Z1-8
COM
TYPE 14: Zone Doubling with Tampers.
Low Zone = Smoke Detector (N/O)*
High Zone = PIR-A (N/C)
2K2
PIR
Tamper
Contacts
Alarm
Contacts N/O
4K7
Smoke
For this hardware configuration the zone must be programmed to be type 14 at address:
P 125 E 1-8=zone number E 14=zone type E
P 122 E 1-16=zone number E On by default
Option 1 = Zone is Active. This should be On unless you don’t wish to use the zone.
Option 2 = Zone is N/O. If the zone is a smoke detector with N/O contacts turn this On.
Option 3 = Not an Exit delay zone. Leave this option Off.
Option 4 = Keypad Zone. If On the standard zone is disabled and wont work.
Option 5 = Radio Zone. If On the standard zone is disabled and wont work.
Option 6 = Stay Mode. If On the zone will activate the alarm if Set in Stay Mode.
Option 7 = Manually Bypass. On means the zone can be disabled from the keypad.
Option 8 = Auto Bypass. If On the zone can auto disable if not sealed on Arming.
1 6 7 8