Ascon Tecnologic - K__V - Indicators - ENGINEERING MANUAL - PAG. 5
3.6 Power Supply
1
2
3
7
8
1
2
13
14
Supply voltage: • 12 VAC/DC (±10%)
• 24 VAC/DC (±10%);
• 100... 240 VAC (±10%).
Power Consumption: 5 VA max.
Notes: 1. Before connecting the instrument to the power
line, make sure that line voltage is equal to the
voltage shown on the identification label;
2. To avoid electrical shock, connect power line at
the end of the wiring procedure.
3. For supply connections use No 16 AWG or larger
wires rated for at last 75 °C.
4. Use copper conductors only.
5. For power supply the polarity is a do not care
condition.
6. The power supply input is NOT fuse protected.
7. Please, provide a T type 1A, 250 V external fuse.
4. TECHNICAL CHARACTERISTICS
4.1 Technical Specifications
Case: Plastic, self-extinguishing degree: V-0 according to UL 94;
Front protection: IP 65 (when the optional panel gasket is
mounted) for indoor locations according to EN 60070-1.
Rear terminals protection: IP 20 according to EN 60070-1.
Terminal block: Screw terminals (screw M3, for cables of
0.25... 2.5 mm
2
or from AWG 22 to AWG 14) with connection
diagrams.
Dimensions:
K3xV: 78 x 35 x 64 mm (3.07 x 1.38 x 2.52”)
K4xV: 48 x 48 x 98 mm (1.77 x 1.77 x 3.86”)
K85V: 70 x 84 x 60 mm (2.76 x 3.31 x 2.37”);
Mount cut-out:
K3xV: 71
(+0.6) x 29(+0.6) mm [2.8(+0.023) x 1.78(+0.023) in.];
K4xV: 45(+0.6) x 45(+0.6) mm [1.78(+0.023) x 1.78(+0.023) in.];
K85V: DIN rail mounting.
Weight: About 180 g;
Power Supply:
– 12 VAC/DC (±10% of the nominal voltage);
– 24 VAC/DC (±10% of the nominal voltage);
– 100... 240 VAC (-15... +10% of the nominal voltage);
Power consumption: 5 VA max.;
Insulation voltage: 2300 V rms according to EN 61010-1;
Display:
One 4 digits red display h 12 mm + 3 LED Bargraph;
Display updating time: 500 ms;
Sampling time: 130 ms;
Resolution: 30000 counts;
Total Accuracy: ±0.5% F.S.V. ±1 digit @ 25°C of room
temperature;
Common mode rejection: 120 dB at 50/60 Hz;
Normal mode rejection: 60 dB at 50/60 Hz;
Electromagnetic compatibility and
safety requirements
Compliance:
- directive EMC 2004/108/CE (EN 61326-1),
- directive LV 2006/95/CE (EN 61010-1);
Installation category: II;
Pollution category: 2;
Temperature drift: It is part of the global accuracy;
Operating temperature: 0... 50°C (32... 122°F);
Storage temperature: -30... +70°C (-22... 158°F);
Humidity: 20... 85% RH, non condensing;
Protections: WATCH DOG (hardware/software) for the
automatic restart.