4. Push and release SET (8) to enter the “SE” menu.
5. Current service interval is displayed.
(“60” or any other value between “0” and “99”)
6. Select desired service interval using the UP or DOWN button.
(40=4000h, 55=5500h, 80=8000h,…)
7. Push and release SET to confirm the new service interval.
8. The selected value blinks during 3 seconds.
9. Then “rS” is fixed and “°C” blinks on display for ~10 seconds.
The new service interval is now set.
Freeze protection function (available with Remote Alarm function on FX 13 to FX 16)
Once the digital controller detects a dewpoint temperature below -2°C during more than 2 minutes, (L2
Alarm), it switches off the refrigerant compressor.
Resetting the dryer after a refrigerant compressor stop (available with Remote Alarm function on FX
13 to FX 16)
Press button 7 to reset the alarm.
The dryer restarts when both the following conditions are true:
The dewpoint temperature is higher than -2°C
30 seconds are passed from the refrigerant compressor stop (minimum balancing pressure stop time).
A countdown is available if the reset is made before the minimum stop time.
Silent alarm function (available with Remote Alarm function on FX 13 to FX 16)
To snooze the alarm, press button 7.
Instruction book
22 2920 7112 50