The fuel is feeded, ignitted, but the ventilator does not start:
Check Remedy
The fuel is feeded, ignitted, ventilator starts, but then the feeder does not start:
CheckRemedy
The appliance stopped, it does not work after restarting:
Check Remedy
When the appliance does not start:
If the appliance does not start in despite of searching for the defects, please, call the
professional service organization.
Fuse of fan motor (damaged) - replace
Ventilator including the cable - test
Motor of ventilator (damaged) - replace
Photocell (dirty) - clean
Photocell (damaged) - replace
Photocell has interrupted its function by inperfect combustion.
Photocell sensitivity, on P5 Check the LD1 during operation
(LD1 should light on, when the flame
is burning in the burner).
Possible operational defect caused by:
- photocell
- heating spiral
- fuses inside the service box
12