SYL-1512A PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL
Version 2.2, July. 2007
Auber Instruments, 730 Culworth, Alpharetta, GA 30022
www.auberins.com e-mail: info@auberins.com Tel: 770-569-8420
WARNING
·Wiring precautions
-Install an external protection circuit if failure of this instrument could result in damage to your system.
-In order to prevent instrument damage or failure, protect the power line and the input/output lines from
high currents by using fuses with appropriate ratings. A very fast blowing fuse (such as an I
2
t fuse) is
needed when the output device is a solid-state relay (SSR). Please check with your fuse supplier for the
correct fuse for your SSR.
·Power supply
-Supply power of the specified rating.
-Do not turn on the power until all of the wiring is completed.
-Never use this instrument in the presence of inflammable gases or vapor.
-In order to prevent electric shock or burns, never touch the inside of the instrument.
-Do not attempt to modify this instrument.
·Maintenance
-Only authorized service engineers should replace parts.
-In order to use this instrument continuously and safely, conduct periodic maintenance. Some parts used
in this instrument have a limited service life and may deteriorate over time.
Caution
·Only clean the instrument when power is off.
·Please use a soft cloth or tissue to clean up stains on the display.
·Never use sharp & hard objects such as screwdrivers or ball pens to touch the buttons on the panel.
=============================================================
1. Features
Compact size, 1/32 DIN that is only 24 x 48 x 75 mm (1x2 x3”)
Supports 10 different types of commonly used temperature sensors, including Pt100 and Cu50 RTDs
TRJBSKEand WRe3-WRe25 thermocouples.
The PID control output can be configured by user for either relay contact or SSR.
The relay contact output can also be configured as the alarm output, or on/off control
Auto-tune function can automatically find the best PID parameters.
Temperature can be displayed in Fahrenheit and Celsius.
Can be used with either DC or AC power source.
Figure 1
2. Specification
Power supply85260VAC or 85360VDC
Power consumption<2W
Sampling rate4 sample/sec
Accuracy0.2% full scale
1
Question and Answer IconNeed help?

Do you have a question about the Auber Instruments SYL-1512A and is the answer not in the manual?

Auber Instruments SYL-1512A Specifications

General IconGeneral
BrandAuber Instruments
ModelSYL-1512A
CategoryTemperature Controller
LanguageEnglish

Related product manuals