Page 5
DURApulse GS20 AC Drive Quick-Start Guide – 1st Ed 06/29/2020
DURApulse GS20 AC Drive Quick-Start Guide
GS20_QSP_1ed 06/29/2020
Entering and Exiting “GS2” Mode
GS20 drives that have an equivalent GS2 model (same power and HP rating) have the option of being operated
in “GS2 Mode”. This allows you to use the new drive in exactly the same role as an older GS2 drive that needs
to be replaced, or in conjuction with existing GS2 drives.
Note that all drives will come factory standard with GS20 mode as the default setting.
Enter GS2 Mode
Note: To enter GS2 mode, parameters cannot be locked or set to read only, and the PLC must be disabled. If
any of these requirements are not met, you will be unable to set 00.02 to 20.
1) Set parameter 00.02=2, to reset to GS2 mode (1st parameter) and press ENTER.
2) Set parameter 00.02=20 to reset to GS2 mode (2nd parameter) and press ENTER.
3) Reboot the drive by cycling power.
4) Configure GS2 parameters per the tables below.
Exit GS2 Mode
1) Set parameter 09.08=20 to reset to GS20 mode (parameters will reset). Press ENTER.
2) Reboot the drive by cycling power.
3) Configure GS20 parameters per the tables above and in the GS20 User Manual.
DURApulse GS2 Parameter Settings
Parameter
Description Settings User
Group #
P00 00 Motor nameplate voltage
115/230V series–200/208/220/230/240
460V series–380/400/415/440/460/480
575V series–380 to 637
P00 01 Motor nameplate amps Drive rated amps times 30 to 100%
P00 02 Motor base frequency 50/60/400
P00 03 Motor base RPM 375 to 9999 rpm
P00 04 Motor maximum RPM Base RPM (parameter 0.03) to 9999 rpm
P01 00 Stop methods 00–Ramp to stop 01–Coast to stop
P01 01 Acceleration Time 1 0.1 to 600.0 seconds
P01 02 Deceleration Time 1 0.1 to 600.0 seconds
P02 00 Volts/Hertz Settings
00–General Purpose
01–High Starting Torque
02–Fans and Pumps
03–Custom
P02 02 Auto-torque boost 00 to 10
P03 00 Source of Operation Command
00–Operation determined by keypad
01–Operation determined by external control. Keypad
STOP enabled.
02–Operation determined by external conrol, keypad
STOP disabled.
03–Operation determined by RS232C/RS-485 interface,
keypad STOP is enabled.
04–Operation determined by RS-232C/RS-485 interface,
keypad STOP is disabled.
P03 01
Multi-function Input Terminals
(DI1 - DI2)
00–DI1=FWD/STOP
DI2=REV/STOP
01–DI1=RUN/STOP
DI2=REV/FWD
02–DI1=RUN momentary (N.O.)
DI2=REV/FWD
DI3=STOP momentary (N.C.)
P03 02 Multi-function Input (DI3)
00–External fault (N.O.)
01–External fault (N.C.)
02–External reset
03–Multi-speed/PID SP Bit1
04–Multi-speed/PID SP Bit2
05–Multi-speed/PID SP Bit3
06–Reserved
07–Reserved
08–Reserved
09–Reserved
10–Ext. Base Block (N.O.)
11–Ext. Base Block (N.C.)
12–2nd Accel/Decel Time
13–Speed Hold
14–Increase Speed
15–Decrease Speed
16–Reset Speed to Zero
17–PID Disable (N.O.)
18–PID Disable (N.C.)
99–Input Disable
P03 03 Multi-function Input (DI4)
P03 04 Multi-function Input (DI5)
P03 05 Multi-function Input (DI6)
P03 11 Multi-function Output Terminal 1
00–AC Drive Running
01–AC Drive Fault
02–At Speed
03–Zero Speed
04–Above Desired Freq.
05–Below Desired Freq.
06–At Maximum Speed
07–Over Torque Detected
08–Above Desired Current
09–Below Desired Current
10–PID Deviation Alarm
P03 12 Multi-function Output Terminal 2
P04 00 Source of Frequency Command
00–Frequency determined by keypad potentiometer
01–Frequency determined by keypad up/down
02–Frequency determined by 0 to +10V input on AI
terminal with jumpers.
03–Frequency determined by 4 to 20 mA input on AI
terminal with jumpers.
04–Frequency determined by 0 to 20 mA input on AI
terminal with jumpers.
05–Frequency determined by RS-232C/RS-485
communication interface.
P04 01 Analog Input Offset Polarity
00–No Offset
01–Positive Offset
02–Negative Offset
P04 02 Analog Input Offset 0.0 to 100.0 %
P04 03 Analog Input Gain 0.0 to 300.0 %
P04 11 Analog Output Signal
00–Frequency Hz
01–Current A
02–PV
P04 12 Analog Output Gain 00 to 200%
DURApulse GS2 Parameter Settings
Parameter
Description Settings User
Group #
P06 31 Present Fault Record
00–No Fault occured
01–Over-current (oc)
02–Over-voltage (ov)
03–Overheat (oH)
04–Overload (oL)
05–Overload 1 (oL1)
06–Overload 2 (oL2)
07–External Fault (EF)
08–CPU failure 1 (CF1)
09–CPU failure 2 (CF2)
10–CPU failure 3 (CF3)
11–Hardware Protection
Failure (HPF)
12–Over-current during accel
(OCA)
13–Over-current during
decel (OCd)
14–Over-current during
steady state (OCn)
15–Ground fault or fuse
failure (GFF)
16–Reserved
17–Input Power 3-phase
loss
18–External Base-Block
(bb)
19–Auto Adjust accel/
decel failure (cFA)
20–Software protection
code (codE)
P06 32 Second Most Recent Fault Record
P06 33 Third Most Recent Fault Record
P06 34 Fourth Most Recent Fault Record
P06 35 Fifth Most Recent Fault Record
P06 36 Sixth Most Recent Fault Record
P07 00 Input Terminal for PID Feedback
00–Inhibit PID operation
01–Forward Acting (Heating Loop) PID feedback, PV from
AVI (0 to +10V)
02–Forward Acting PID feedback, PV from ACI (4 to 20
mA)
03–Reverse Acting (Cooling Loop) PID feedback, PV from
AVI (0 to +10V)
04–Reverse Acting PID feedback, PV from ACI (4 to 20 mA)
P07 02 PID Setpoint Source
00–Keypad
01–Serial Communication
P07 20 Proportional Control 0.0 to 10.0
P07 21 Integral Control 0.00 to 100.0 seconds (0.00=disable)
P07 22 Derivative Control 0.00 to 1.00 seconds
P08 00 User Defined Display Function
00–Output Frequency (Hz)
01–Motor Speed (rpm)
02–Output Freq. X P8.01
03–Output Current (A)
04–Motor Output Current (%)
05–Output Voltage (V)
06–DC Bus Voltage (V)
07–PID Setpoint
08–PID Feedback (PV)
09–Frequency Setpoint
P08 01 Frequency Scale Factor 0.01 to 160.0
P09 08 Restore to Default
20–Reset to GS20 mode
99–Restore ALL parameters to factory defaults
Cooling and Heat Dissipation
Airflow Rate for Cooling Power Dissipation (Watts)
Model
Number
Flow Rate
(cfm)
Flow Rate
(m
3
/hr)
Loss External
(Heat sink)
Internal Total
GS21-10P2
0.0 0.0
8.0 10.0 18.0
GS21-10P5
14.2 13.1 27.3
GS21-11P0
16.0 27.2 29.1 23.9 53.0
GS21-20P2
0.0 0.0
8.0 10.3 18.3
GS21-20P5
16.3 14.5 30.8
GS21-21P0
29.1 20.1 49.2
GS21-22P0
16.0 27.2
29.1 23.9 53.0
GS21-23P0
70.0 35 105
GS23-2010
53.7 91.2
244.5 79.6 324.1
GS23-2015
374.2 86.2 460.4
GS23-2020
67.9 115.2 492.0 198.2 690.2
GS23-20P2
0.0 0.0
8.6 10.0 18.6
GS23-20P5
16.5 12.6 29.1
GS23-21P0
31.0 13.2 44.2
GS23-22P0
10.0 16.99 50.1 24.2 74.3
GS23-23P0
16.0 27.2
76.0 30.7 106.7
GS23-25P0
108.2 40.1 148.3
GS23-27P5
23.4 39.7
192.8 53.3 246.1
GS23-4010
164.7 55.8 220.5
GS23-4015
53.7 91.2
234.5 69.8 304.3
GS23-4020
319.8 74.3 394.1
GS23-4025
67.9 115.2
423.5 181.6 605.1
GS23-4030
501.1 200.3 701.4
GS23-40P5
10.0 16.99
17.6 11.1 28.7
GS23-41P0
30.5 17.8 48.3
GS23-42P0
45.9 21.7 67.6
GS23-43P0
16.0 27.2
60.6 22.8 83.4
GS23-45P0
93.1 42 135.1
GS23-47P5
23.4 39.7
132.8 39.5 172.3
GS23-5010
108.4 51 159.4
GS23-51P0
0.0 0.0 23.5 12.5 36
GS23-52P0
10.0 16.99 38.1 19 57.1
GS23-53P0
16.0 27.2
56.6 22.2 68.8
GS23-55P0
76.1 30 106.1
GS23-57P5
23.4 39.7 93.9 37 130.9
• External Flow Rate is across the heat sink.
• Internal Flow Rate is through the chassis.
• Published flow rates are the result of active
cooling using fans, factory installed in the
drive.
• Unpublished flow rates ( - ) are the result
of passive cooling in drives without factory
installed fans.
• The required airflow shown in the chart
is for installing a single GS20 drive in a
confined space.
• When installing multiple GS20 drives,
the required air volume would be the
required air volume for a single GS20 drive
multiplied by the number of GS20 drives.
• When calculating power dissipation (Watt
Loss), use the Total value. Heat dissipation
shown in the chart is for installing a single
GS20 drive in a confined space.
• When installing multiple drives, the volume
of heat/power dissipation should be the
heat/power dissipated by a single GS20 drive
multiplied by the number of GS20 drives.
• Heat dissipation for each model is calculated
by rated voltage, current and default carrier
frequency.