Line of Sight Infrared Hydrocarbon Gas Detector AutroPath HC800 , 116-P-HC800/IGB, Rev. A, 2016-03-03
P/N 95-8744, v4.2 , rev. 3/16
Autronica Fire and Security AS
Page 36
Additional Safety Notes:
• For ambient temperatures below 10°C, use eld wiring suitable for the expected conditions, and for ambient
temperatures above +6C, use field wiring and cable glands suitable for 15°C above the maximum expected
conditions.
ATEX Standards:
EN 60079-29-4: 2010
Performance Approved for Methane, Butane, and Propane
EN 60079-0: 2012 +A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-28: 2007
EN 60529:1991+A1: 2000
EN 50270: 2015
EN 50271: 2010
ACCurACy (per en 60079-29-4)
±5% of full scale gas concentration or ±10% of applied gas concentration, whichever is greater.
RESPONSE TIME
T90: 2 seconds (2.5 LFL-meters applied).
ALIGNMENT
Misalignment will cause the manufacturer stated accuracy limits to increase, but remain within the limits of EN
60079-29-4.
Accessories with the following part numbers are approved for use with the AutroPath HC800:
116 - 0117 73 - 0 01 Short Range Aperture Kit
116 - 012287-XXX AutroPath HC800 Alignment Tool
116 - 009246-002 Gas Test Cell
116 - 012673-001 System Test Film
116 - 012312-001 Transmitter Brow
116 - 012300-001 Receiver Brow
116 - 012660-001 Mounting Bracket
116 -103922-001 HART Handheld Communicator
116 - 011824-001 Modbus Program
116-102740-002 Calibration Magnet