Maintenance
Avtron Outdoor Resistive Load Bank • Part Number K975A 994213
5-1
SECTION V
MAINTENANCE
To provide long equipment life and to reduce the chance of electric shock, fires, and personal injury,
good maintenance procedures must be used. Before servicing, review the SAFETY
CONSIDERATIONS section of this manual.
The following examples of scheduled maintenance procedures are not intended to be all-inclusive
but must be accomplished to maintain the equipment in a good, safe condition. All maintenance
work must be done only by qualified personnel.
*************************************************************
W A R N I N G
Personal injury from electrical shock or from the moving fan blades
may result if ALL sources of power are not disconnected. Refer to
the SAFETY CONSIDERATIONS section of this manual.
Eye protection should be worn when cleaning the unit with
compressed air.
*************************************************************
DAILY
1. Remove any restrictions to the airflow through the Load Bank.
2. Check the screens to make sure that no objects have blocked or entered the openings.
3. Verify that the airflow is in the proper direction.
4. Assure that there is no recirculation of the exhaust air through the Load Bank.