Installation
Avtron Resistive Load Bank - Part Number LPV600 994210
3-1
SECTION III
INSTALLATION
BEFORE INSTALLATION
Inspect the Load Bank for obvious damage such as broken wires, broken or dented panels, cracked
ceramic insulators, or any other component breakage that may have occurred in shipment.
LOCATION
The Load Bank is designed primarily for indoor use. The Load Bank must be used in a cool, well
ventilated area. It must be installed where cool air is continually available and where hot exhaust air
will not be recirculated through the Load Bank. If the Load Bank is operated in a closed space,
continuous ventilation of 15,000 CFM or greater is required.
A minimum of four (4) feet of clearance from all sides and twelve (12) feet of clearance on the
exhaust end are required for proper airflow.
*************************************************************
W A R N I N G
The exhaust air will be in excess of 350
o
F above ambient under full
load conditions. The unit must not be installed near any equipment,
wiring or plumbing which may be damaged by high air temperatures
or which may constitute a fire hazard. Care should also be taken so
as not to set off a sprinkler system by exposing it to hot exhaust air.
*************************************************************
DO NOT STACK LOAD BANKS.
Standard Load Bank design is suitable for operation between sea level and 2,000 ft. maximum
altitude.