Installation
Avtron Resistive Load Bank - Part Number LPV600 994210
3-4
GROUNDING
A permanent ground should be connected to the Load Bank enclosure either by a grounded conduit
or with a separate ground wire to prevent a potential above ground on the enclosure. No internal
ground connections are made to any terminal on the Load Bank.
The ground conductor should be run with the load power conductors to provide the lowest
impedance fault path. The ground stud within the Load Bank (located on floor near cable cutout)
must be connected to both the generator frame and a good earth ground. The ground conductor
should be sized for National Electric Code section 250-95 if not superseded by local codes.
*************************************************************
W A R N I N G
Do not operate the Load Bank with any panel or screen removed or
any doors open. This may expose the operator to dangerous high
voltage and the rotating fan blade, as well as disrupting the airflow.
Keep both of the front hinged covers and both resistor hinged covers
closed and latched.
*************************************************************
STORAGE
The Load Bank should be covered to limit long term effect of moisture and to reduce the
accumulation of dust, dirt, and debris. The unit should be stored in a dry, enclosed area. An
optional waterproof vinyl cover is available for the Load Bank; however, even with this cover, the
Load Bank should not be stored outdoors permanently.