[3. FM intrinsically safe]
Select an installation location for an FM intrinsically safe model in accordance with the
following criteria.
• Hazardous areas in which this device can be installed are defined as follows.
[Intrinsically safe]
Class I, II, III, Division 1, Group A, B, C, D, E, F, G, T4
[Intrinsically safe]
Class I, Zone 0, AEx ia IIC T4, Ta = 80°C
[Non-incendive]
Class I, Division 2, Group A, B, C, D, and T5, Ta = 80°C
[Suitable]
Class II, III, Division 2, Groups F,G, T4, Ta = 80°C
*NEC: NFPA70 - National Electric Code. For details, see the text of the NEC.
Dustproof and waterproof performance specifications: TYPE 4X, IP66
Ambient temperature range: −40 to +80°C
Perform electrical wiring work in accordance with NEC.
Gases with an ignition point of 135°C or higher
Ambient atmosphere of acetylene, ethylene, propane, etc.; ambient
atmosphere of metal dust, coal or carbon black dust, grain dust
Division 1 or 2 hazardous area according to NEC, article 500*
Gas and flammable dust
For flammable fibers
Gases with an ignition point of 135°C or higher
Class IIC explosive gases
Zone 0, 1 or 2 hazardous area according to NEC, article 505*
For gas
Gases with an ignition point of 100°C or higher
Ambient atmosphere of acetylene, hydrogen, ethylene, propane, etc.
Division 2 hazardous area according to NEC, article 500*
For gas
Gases with an ignition point of 135°C or higher
Ambient atmosphere of carbon black dust or grain dust
Division 2 hazardous area according to NEC, article 500*
Flammable dust
For flammable fibers