EasyManua.ls Logo

Azbil TY6800Z7000 - TTY6800 Z Control Modes; TTY6800 Z Setpoint and Differential Gap; TTY6800 Z Cooling Two-Step Control

Azbil TY6800Z7000
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
15
AB-6600
z
Model TTY6800Z
As shown in Figure 27. Setpoint and differential gap for Model TTY6800ZE, the differential gap of each switch
is xed to 3 °C.
A dial for setting the setpoint is placed above the switch 1. Differential between two switches can be set
approx. in 2.5–8 °C range.
Figure 27. Setpoint and differential gap for Model TTY6800Z
< Cooling two-step control >
Based on the cooling control system shown in Figure 17. Example of wiring for cooling two-step control,
two chillers are installed. Operation of Model TTY6800Z thermostat is described assuming the temperature
setpoint: -10 °C, differential gap: 3 °C, differential between two switches: 8 °C.
(1) When the temperature of the controlled target rises to the setpoint (-10 °C), the switch 1 works to close the
terminal R1 and W1, and then the chiller 1 starts.
(2) Along with operation of chiller 1, when the temperature of the controlled target falls to -13 °C, that is
setpoint (-10 °C) minus differential gap (3 °C), the switch 1 works to open the terminal R1 and W1, and
then the chiller 1 stops.
(3) Although the chiller 1 keeps operating, if the temperature of the controlled target keeps rising and it
reaches -2 °C, that is setpoint (-10 °C) plus the differential between two switches (8 °C), the switch 2 works
to close the terminal R2 and W2, and then the chiller 2 starts.
(4) Along with operation of chiller 1 and chiller 2, when the temperature of the controlled target falls to -5 °C,
that is chiller 2 triggered temperature (-2 °C) minus the differential gap (3 °C), and then the chiller 2 stops.
Only the chiller 1 operates.
(5) When temperature of the controlled target falls further to -13 °C, that is setpoint (-10 °C) minus the
differential gap (3 °C), and then the chiller 1 stops.
(6) When the temperature of the controlled target rises again, the steps from (1) will be carried out
automatically.
Figure 28. Example of cooling two-step control
[°C]
Sensor (ambient temp.)
Temperature rise
Sensor (ambient temp.)
Temperature fall
Switch 1
Differential gap
3 °C (fixed)
Switch 2
Differential gap
3 °C (fixed)
Differential between two switches
Approx. 2.5-8 °C (variable)
Differential between two switches
Approx. 2.5-8 °C (variable)
Setpoint
Between terminal R1 and W1: Open
Between terminal R1 and B1: Close
Between terminal R1 and W1: Close
Between terminal R1 and B1: Open
Between terminal R2 and W2: Close
Between terminal R2 and B2: Open
Between terminal R2 and W2: Open
Between terminal R2 and B2: Close
Temperature of sensor [ °C]
-10
(Setpoint)
-2-5-13
(2) (1),(5)
(4) (3)
Chiller 1 ON
Between R1 and W1: Close
Between R1 and B1: Open
Chiller 1 OFF
Between R1 and W1: Open
Between R1 and B1: Close
Chiller 2 ON
Between R2 and W2: Close
Between R2 and B2: Open
Chiller 2 OFF
Between R2 and W2: Open
Between R2 and B2: Close
Switch 2
Differential gap
3 °C
Differential between two switches
8 °C
Switch 1
Differential gap
3 °C

Related product manuals