Parameter 3
Terms of Entry defrosting
function (-30 to 0 ,
default setting -7℃)
℃ ℃
Parameter 2
Total working time of
compressor after frosting
(30-90MIN ,default
setting : 40MIN)
Parameter 0
To set the entering water
temp. under cooling mode
(8-35℃,default setting:
28℃)
Parameter 1
To set the entering water
temp. under heating mode
(15-35℃, default
setting:28℃)
Parameter 4
Terms of Exit defrosting
function (2 to 30 ,
default setting 13℃)
℃
Parameter 5
Time of Exit defrosting (1 to
12MIN, default setting 8MIN)