The Bacharach
®
AGMSZ (Ammonia Gas Monitor Single
Zone) is an infrared detector based unit designed for
continuous single-point monitoring of ammonia gas. The
unit displays both the current and peak gas levels. Gas
alarms and fault conditions are indicated by audible and
visual alarms. The AGMSZ’s four relay contacts enable
external devices to be triggered when gas alarms or fault
conditions occur. A 4-20mA output enables the unit to
be integrated with remote monitoring equipment or
building management systems.
FEATURES
• Small in size, big in value
• False alarms are virtually eliminated with the use of
infrared detection technology
• Three gas alarm levels can be individually set by
the user
• Logging feature enables 200 gas readings to be stored
at user-selectable time intervals
• Two year warranty
SPECIFICATIONS AGMSZ
Measures: Ammonia (NH
3
, also known as R-717)
Inputs: Dedicated Single Zone
Output Signal: 3 SPDT, 5 Amp, 240 VAC rated alarm relays and 1SPDT,
5 Amp, 240 VAC rated system fault relay, plus a Digital
Display w/ a dedicated 4-20 mA DC analog output
(floating ground)
Detector Type: Single Pass, Non-dispersive Infrared
Measuring Range: 25 to 10,000 ppm
Sensitivity: 1ppm
Accuracy: ±10ppm from 25 to 100ppm, ± 10% of reading from
100 to10,000ppm
Front Panel Display: Green LED indicates when unit is operating properly
Red LED indicates when any monitored point is above
any of its alarm settings
Yellow LED indicates a clogged sample line or other
system fault
Response Time: 9 to 30 seconds, depending on sample tube length
Max. Monitoring Distance: Up to 50 feet from measuring point to monitor
Power: 120 to 240 VAC, 50/60 Hz
Size/Weight: 14” x 18” x 4.5” / 7 lbs.
(35.6cm x 45.7cm x 11.4cm / 3.2Kg)
ORDERING INFORMATION
PART NO. DESCRIPTION
3015-4280 AGMSZ single zone monitor (includes
1 termination filter, 50ft. of 304-2742
sample line tubing and 50ft. of 304-
2743 exhaust / purge line tubing)
304-2742 Sample tubing for AGMSZ
3015-3420 Termination filter
304-2743 Exhaust / purge line tubing (note: tubing
304-2742 is required for AGMSZ sample line)
3015-4121 120 VAC surge protector
3015-4122 220 VAC surge protector
3015-4123 4-20mA surge protector
3015-3070 120 VAC external audible alarm
3015-3069 120 VAC external visual alarm
3015-3076 120 VAC external audible / visual alarm
* Special delivery terms. Call factory for details.