FEATURES
PROTECTION
Phase, Neutral, and Negative Sequence
Instantaneous Overcurrent elements with settable
time delay: 50TP, 150TP, 50TN, 150TN, 50TQ,
150TQ
Phase, Neutral, and Negative Sequence Time
Overcurrent elements: 51P, 51N, 51Q
All U.S. and IEC timing curves plus user program-
mable curve
Responds to either Average AC, Fundamental, or
Wide band RMS to 7th harmonic
Minimizes transient overreach and overtravel on
overcurrent elements
Separate ground current input
Breaker Failure protection function: BF
Two general purpose logic timers: 62, 162
Programmable Logic using BESTlogic
Four protection setting groups with external or
automatic (cold load pickup, load, unbalance,
recloser shot) selection modes
CONTROL
Four shot recloser with zone sequence coordina-
tion and sequence controlled protective element
blocking functions
Virtual breaker control switch—controllable from
both HMI and com. ports: 101
Four virtual selector switches—controllable from
both HMI and com. ports: 43, 143, 243, 343
INSTRUMENTATION
Real time A, B, C phase, neutral, and negative
sequence currents
1% meter accuracy down to 10% of nominal current
REPORTS
Current demands for phase, neutral, and negative
sequence currents—magnitudes and time stamps
are recorded for today's peak, yesterday's peak,
and peak since reset
Breaker operations counter and contact
interruption duty
FAULT RECORDING
255 event sequence of events report with I/O and
alarm sub-reports
Fault Reporting; 1 or 2 oscillography records per
fault report
Fault summary reports; two most recent Fault
Summary Records saved to non-volatile memory
16 fault records, 15 cycles long @ 24 samples/
cycle
COMTRADE format
COMMUNICATION PORTS
Three independent general purpose communica-
tion ports
- Front RS-232 ASCII communications
- Rear RS-232 ASCII communications
- Rear RS-485 ASCII, Modbus
, DNP or other common
protocols
IRIG-B time sync (unmodulated)
SELF TEST AND ALARM FUNCTIONS
Relay fail, major alarm, and minor alarm LEDs,
and fail-safe alarm output contact (optional
normally open or normally closed)
Extensive internal diagnostics monitor all internal
functions of the relay
More than 20 additional alarm points—
programmable for major or minor priority
Including:
- Reclose fail and lockout
- Phase demand overload alarm
- Neutral and negative sequence unbalance demand
alarms
- Three breaker alarm points—programmable for slow
trip, interruption duty threshold, or operations counter
- Trip circuit voltage and continuity monitor
- Close circuit monitor via BESTlogic
PROGRAMMABLE I/O
Four programmable inputs
Seven programmable outputs and one dedicated
programmable alarm output
HARDWARE FEATURES
Full drawout
- H1:Half-rack
Active CT technology for low burden and
increased dynamic range
Flash Memory for upgrading embedded
programming without changing chips
Real Time Clock with 8 hour capacitor ride
through and optional battery backup
Integral HMI with 2x16 character display
Wide range ac/dc power supply options provide
long hold up time to ride through dips on ac
power source. (100 ms with 4 output relays
energized, upon complete loss of source. Starting
voltage 125Vac for Option 1 (48/125Vac/dc) and
250Vac for Option 2 (125/250Vac/dc))